AE200 Fault finding

Common Issues with the AE200 Controller:

Firmware Mismatches When Linking Controllers:Faults on the AE200 controller itself are rare, but problems will arise when multiple controllers are linked together with differing firmware versions.Ensuring that all linked controllers have the same firmware version is critical to avoid such issues. Hence firmware updates have been covered in the training to ensure compatibility across systems.

6607 Fault (Addressing Error):

This fault typically occurs when an indoor unit that dosent exist is added to a group or if the indoor unit isn’t powered on.Double-check that the indoor unit is properly powered. Does that the indoor unit exist on the M-net (Communication cable).