CAHV function changes
CAHV Commissioning waterside
M-NET control for Cascade - SW5 - 6 ON for the main unit & OFF on the sub units.TH16 temperature sensor - SW5 - 8 ONSolo CAHV - SW5- 9 to OFFCascade CAHV units SW5 - 9 to ON (only on the main unit) Changes will only be accepted once unit is powered off and on again.
Read more