All inputs MUST be Volt-free/
Connected via Volt-free Relay
SW1-7 MUST BE ON = Monobloc Heat Pump In Use
SW2-8 MUST BE ON = Flow Sensor In Use


The guidance below applies to the FTC6 (Indoor Unit). Turn ON relevant DIPS as shown below, all remaining DIPS to be OFF.
FTC6 Commissioning GUIDE
For Single Heat Pump / Basic Applications OnLY
After completing the commissioning wizard, go into Initial Settings and set the Room Sensor Settings:
• If using Mitsubishi Electric Wireless Room Stat(s), select Room RC.
• If using the Main RC itself, 3rd-Party Room Stat or Underfloor Wiring Centre, select Main RC.
Room Sensor Settings
SW1-8 ON = Mitsubishi Electric Wireless Room Stat(s) In Use. (Maximum of 8)
SW2-1 ON = 3rd-Party room stat or underfloor wiring centre controlling Heating Zone 1 via IN1
SW3-1 ON = 3rd-Party room stat or underfloor wiring centre controlling Heating Zone 2 via IN6
SW5-2 ON = Advanced Auto Adaption Mode Active (Only compatible with Mitsubishi Electric wireless room stats)
Heating Controls
SW3-5 ON Only = Single Heating Zone
SW3-5 & SW3-6 ON = 2x Heating zones with the same flow temperature
SW3-5, SW2-6 & SW2-7 ON =
2x Heating zones/ different flow temperatures/ FTC controlling blending valve for zone 2 only
Heating Mode
Essential Settings
SW1-3 ON = Domestic Hot Water Mode Active
SW1-4 ON = FTC to control Immersion Heater for Legionella prevention and as back-up if an error occurs
SW3-7 ON = Mitsubishi Electric Pre-plumbed Cylinder In Use.
(Leave SW3-7 OFF for Coil Cylinders)
Hot Water Mode