PRESSURE TESTING SAFETY TRAINING
Start
OVERVIEW & PURPOSE:
This training is made to
ensure that working
personnel involved in
HIGH-PRESSURE SYSTEM testing have knowledge of the
hazards and dangers
associated with the said
activity.
Index Page
Objectives
OBJECTIVES:
- By the end of this session, participants will know the definition of
hydrotesting and the difference to other testing conducted on site.
- In the end of the training, participants will have an idea regarding
the purpose in line with the other construction activities.
- This training will ensure that attendees will be able to recognize the hazards of hydrotesting activities
- By the end of this training participants will remember the safety
precautions they need to establish to avoid injuries related to the
known hazards.
- Through this training, participants will also be able to know the DO’s and DON’TS of hydrotesting activities.
- By the end of this training the attendees will able to apply the
safety measures to be discuss in the course as part of their duties
assigned as a hydrotesting involved personnel.
Definition
Index Page
HYDROTESTING DEFINITION:
- The hydro test is the test that is carried out by using water. Water is pressured using the hand/engine pump to a certain
pressure and has to put the system on hold
for some time to observe any leak or failure. If it falls after achieving the required pressure, it means having some problems in the system.
- Hydrostatic testing involves filling the vessels,
pipeline, or system (which need to be tested)
with water, then pressurizing with a hydraulic
pump until the test pressure reaches (normally
1.5 times design pressure), holding the pressure
for a specified time by shutting off the supply
valve and checking for any leakage or pressure
drop. If the pressure drops beyond the standard
tolerable limit, the test is declared FAILED.
Incident Case #01
Index Page
Safe connection
INCIDENT CASE #01:
Emptying of a Vertical Tank
- While the tank was being emptied, it
suddenly collapsed. Root cause analysis shows that a plastic sheet that was protecting the roof was trapped in the vent
which created a vacuum.
- So it is a must to inspect the
venting systems before filling and emptying operations.
There was no injury. It should be noted that this type of
incident is not that unusual.
Incident Case #02
Index Page
INCIDENT CASE #02:
Hydrotest of a New Vertical Vessel
- The image shows an exploded vessel that happened
during hydro testing of a new vessel. The root cause of the incident is
not known fully. But there was some brainstorming and people thought that hydro-testing with “very cold” water could be a contributing
factor. The good news is that no injuries occurred.
- Learning from the Incident
It is learned that water temperature during hydro testing is critical. It
is suggested to maintain the metal and water temperature at least at
16°C or at least 10°C above the impact test temperature of the metal
during pressure testing.
Index Page
Incident Case #03
INCIDENT CASE #03:
Water Filling of a New Vertical Tank
- This incident happened while filling the tank with water from a fire hydrant. As the relief valve could
not displace the air fast enough for the volume of water that was being pumped in, The top of the tank blew off suddenly.
- Fortunately, no injury happened, but an operator was on
top of the tank a few seconds before.
- Top of tank blew off during hydrotesting
Incident Case #04
Index Page
INCIDENT CASE #04:
Sphere Tank Collapse During Hydrotesting
- During the filling of a 2000 m3 LPG
sphere, Its legs suddenly
collapsed. One nearby person was
killed and one was seriously injured.
The research found that the sphere
was approximately 80% full of
fresh water. The vessel’s last hydro test was 10 years ago and the last inspection
of its legs was done 5 years ago.
The main cause was the Severe corrosion
of the legs under the concrete fire
protection. The corrosion occurred due
to water ingress between the concrete and
the steel legs. The water protective cap
that was located over the concrete was not
sufficient to keep the water out. It was
verified later that the steel legs had its
thickness reduced by up to 8 mm, with
pitting holes of up to 10cm2.
Index Page
Next Page
INCIDENT CASE #04:
Sphere Tank Collapse During Hydrotesting
- Thorough investigation and tests confirmed that the following
factors contributed to the sphere collapse:
1. Poor design of the water caps over the fire-proofing concrete was allowing the water to penetrate the steel beams and the concrete. 2. Vertical cracks in the concrete let water in. 3. Poor workmanship during Repairs had been done to the concrete. 4. The new concrete had not adhered to the old concrete, again letting water in. 5. The deluge system had been tested with saltwater, increasing the possibility of corrosion.
- Learning from the incident
A complete inspection must be performed visually and if required with
NDT before pressure testing of an old vessel. This inspection must include
the vessel, nozzles, appurtenances, and supporting structures.
Testing Purpose
Index Page
PRESSURE TESTING PURPOSE:
- Identify the leaks.
- To check the strength of the welded joint.
- To check the capacity of the system.
- To complete it SAFELY.
Testing Hazards
Index Page
HYDROTESTING HAZARDS:
- Inadvertently/suddenly
increase of pressure due
to underrated or
non-calibrated pressure
gauges.
- Substandard support.
- PSV failure.
- Breaking/failure of line,
gasket, flanges, and
gauges.
- Air entrapment inside
the pipe.
- Usage of an engine
operated pump.
Safety Measures
Index Page
HYDROTESTING SAFETY MEASURES:
Hydrostatic testing is a risky process as it
involves pressurizing the system with high
pressure which can fail and cause serious
personal injury or property damage.
Although testing is performed under the
supervision of a competent person, the
following is the risk associated with
hydrostatic testing;
In the event of a leak or burst, a person can
be injured by exposure to high pressure
liquid. High pressure fluid can tear the skin
and damage internal organs.
The pressure hose connection of hydraulic
pump to test piping/ vessels can be
detached and may hit a person nearby.
Training Video
Index Page
INCIDENT VIDEOS
INCIDENT VIDEOS
To control the above hazards, appropriate safety precautions must be ensured while
performing pressure testing.
- The hydrostatic test must only be performed under
the supervision of a competent person.
- Only
essential and trained persons shall be allowed at the pressure test work location.
- Follow the permit to work system and establish
communication.
- Barricade the area to restrict the man movement
and display caution boards to alert people.
- Provide whip latch arrester to secure the hoses
connection.
- Equipment and accessories used for pressure build-up
and inspections must be certified and calibrated.
- Calibrated pressure gauges and Pressure safety
valves only shall be used.
- Rating of fittings, pressure gauges, vent valves,
gaskets shall be suitable for the test pressure.
- Flanges and Plates shall be as per the line class.
Next Page
Index Page
- All the temporary welding shall be performed by qualified
welders and approved by Client QA/QC.
- Ensure air vent provided at the highest elevation.
- Gradual filling of lines shall be done keeping vent to open.
- Ensure that the line is vented to remove air pockets before
pressurization.
- Pressure should be raised gradually under control to allow
time for pipes to strain and time for personnel to check for
leaks.
- There shall be at least two pressure gauges, one at lowest
point and another at the highest point in the system.
- Pressure testing crew should not stay in the direction of the
blind flanges to prevent injury in case of flange rapture.
- All hoses/ piping/gaskets and connectors/clamps shall be
of adequate rating to withstand pressure.
- Personnel shall not approach the system under high Pressure.
- Access shall be free from any obstacle.
- Supervisors shall be present at work location during hydro
testing activities are done.
- Risk assessment shall be done for any pressure testing job.
DO's
- Follow the permit to work system and communicate the associated hazards to engaged
manpower.
- Perform hydrostatic test under the supervision of a competent person only.
- Clearly mark the scope of hydrotest on P&ID and ensure positive isolation of equipment
and piping that are not included in the hydrostatic test loop.
- Inspect all test equipment and tools, even if they are brand new.
Check the design pressure of equipment such as vessel, piping, etc. before the test.
- Ensure calibration of pressure measuring instruments and tools.
- All fittings must be rated above the maximum hydrostatic pressure. *Ensure the setting and calibration of safety relief valve.
- Install at least two pressure gauges at an appropriate place so that it is easily readable.
- Isolate, barricade the test area with safety signage in local and English language.
- If possible, perform the test from a remote area.
Make sure that all pipeline and vessel supports are firm, in good condition and have been
inspected prior to start hydrotest.
- Start the de-pressurization by gradually opening the vent valve.
Open the lowest drain point to remove water from the vessel, pipeline, etc.
- Always wear appropriate personal protective equipment (PPEs).
VS
Index Page
Testing Failures
DON'TS
- Don’t monitor the pressurization step directly in front of the pressure gauges.
- Don’t forget to remove the air pockets through the vent line.
- Don’t attempt to tighten the bolts if the flange leaks during hydrotesting and system is
pressurized.
- Don’t open the drain valve if the vent valve is closed. *Don’t use a pressure gauge with under rated capacity. *Don’t allow unauthorized person to enter the test area.
- Don’t forget to obtain work permit and wear appropriate PPEs.
- Don’t leave any electrical equipment without adequate protection
- Don’t leave the remaining/ residual pressure trapped inside the pipeline or vessel after
testing.
- Don’t forget to provide proper access and egress for work at height.
- Don’t drain the hydrotest water on the floor, make sure there is adequate drainage.
- Don’t miss to isolate monitoring devices/ site glass. *Don’t allow other activities in the vicinity of the hydrotesting work area.
VS
Testing Failures
Index Page
Pressure Vessel Failure During Air Test
Pneumatic Test Incident
Jan 26 2006..accident occurred in a factory in Brazil, during pneumatic pressure testing with Air from pipe work around a tank.
There were no blind flanges are placed in order to isolate the pipe
work to the tank, only the valves were closed. Probably has one or
more valves failed, or were not closed, and the tank also has
undergone a pressure test.
As a result, there has been a tremendous energy built up in the tank, and the tank launched and ended up on top of the installation.
Index Page
Calculating SaFE DISTANCE FOR PRESSURE TESTING SAFE DISTANCE = (0.15) x (D) x (A) / 0.4 x (P) / 0.6 (D) - INTERNAL PIPE DIAMETER (A) - LENGHT/DIAMETER OF THE PIECE (P) - TEST PRESSURE (BAR)
https://hsseworld.com/pressure-testing-and-safe-distance-calculation/
https://www.piping-world.com/safe-distance-and-stored-energy-calculator-pneumatic-test
THANK YOU!
Pressure Testing Safely Training
Remy Villegas
Created on January 30, 2022
Hydrotesting Safety Training Slide
Start designing with a free template
Discover more than 1500 professional designs like these:
View
Corporate Christmas Presentation
View
Snow Presentation
View
Winter Presentation
View
Hanukkah Presentation
View
Vintage Photo Album
View
Nature Presentation
View
Halloween Presentation
Explore all templates
Transcript
PRESSURE TESTING SAFETY TRAINING
Start
OVERVIEW & PURPOSE:
This training is made to ensure that working personnel involved in HIGH-PRESSURE SYSTEM testing have knowledge of the hazards and dangers associated with the said activity.
Index Page
Objectives
OBJECTIVES:
Definition
Index Page
HYDROTESTING DEFINITION:
Incident Case #01
Index Page
Safe connection
INCIDENT CASE #01:
Emptying of a Vertical Tank
Incident Case #02
Index Page
INCIDENT CASE #02:
Hydrotest of a New Vertical Vessel
Index Page
Incident Case #03
INCIDENT CASE #03:
Water Filling of a New Vertical Tank
Incident Case #04
Index Page
INCIDENT CASE #04:
Sphere Tank Collapse During Hydrotesting
Index Page
Next Page
INCIDENT CASE #04:
Sphere Tank Collapse During Hydrotesting
- Thorough investigation and tests confirmed that the following
factors contributed to the sphere collapse:
1. Poor design of the water caps over the fire-proofing concrete was allowing the water to penetrate the steel beams and the concrete. 2. Vertical cracks in the concrete let water in. 3. Poor workmanship during Repairs had been done to the concrete. 4. The new concrete had not adhered to the old concrete, again letting water in. 5. The deluge system had been tested with saltwater, increasing the possibility of corrosion.Testing Purpose
Index Page
PRESSURE TESTING PURPOSE:
Testing Hazards
Index Page
HYDROTESTING HAZARDS:
- Breaking/failure of line,
gasket, flanges, and
gauges.Safety Measures
Index Page
HYDROTESTING SAFETY MEASURES:
Hydrostatic testing is a risky process as it involves pressurizing the system with high pressure which can fail and cause serious personal injury or property damage. Although testing is performed under the supervision of a competent person, the following is the risk associated with hydrostatic testing;
In the event of a leak or burst, a person can be injured by exposure to high pressure liquid. High pressure fluid can tear the skin and damage internal organs.
The pressure hose connection of hydraulic pump to test piping/ vessels can be detached and may hit a person nearby.
Training Video
Index Page
INCIDENT VIDEOS
INCIDENT VIDEOS
To control the above hazards, appropriate safety precautions must be ensured while performing pressure testing.
Next Page
Index Page
DO's
VS
Index Page
Testing Failures
DON'TS
VS
Testing Failures
Index Page
Pressure Vessel Failure During Air Test
Pneumatic Test Incident Jan 26 2006..accident occurred in a factory in Brazil, during pneumatic pressure testing with Air from pipe work around a tank. There were no blind flanges are placed in order to isolate the pipe work to the tank, only the valves were closed. Probably has one or more valves failed, or were not closed, and the tank also has undergone a pressure test. As a result, there has been a tremendous energy built up in the tank, and the tank launched and ended up on top of the installation.
Index Page
Calculating SaFE DISTANCE FOR PRESSURE TESTING SAFE DISTANCE = (0.15) x (D) x (A) / 0.4 x (P) / 0.6 (D) - INTERNAL PIPE DIAMETER (A) - LENGHT/DIAMETER OF THE PIECE (P) - TEST PRESSURE (BAR)
https://hsseworld.com/pressure-testing-and-safe-distance-calculation/
https://www.piping-world.com/safe-distance-and-stored-energy-calculator-pneumatic-test
THANK YOU!