BC Box Addressing
Main BC Box addressing has to follow on from the Outdoor unit addressing sequence. If the main outdoor unit is addressed as 051 and there is only one outdoor unit, the main BC box would be address 052. If the system consisted of two outdoor units and one BC box the addressing would be:
Main BC Box
Outdoor Main - 051Outdoor Sub - 052 Main BC Box - 053
Sub BC Box Addressing
Sub BC Box
Sub BC Boxes are addressed according to the Lowest addressed Indoor Fan coil connected to the Sub Box(Lowest fan coil + 50) For Example: Main OC - 051 Sub OC - 052 Main BC - 053 Indoors connected to main BC 001 to 016 Indoors connected to Sub BC 017 to 020 Sub BC - 067 (017+50)
Lowest IC on Sub Box = 017017 + 50 = 067 Sub BC Box Address
BC Box Addressing
daniel.hodson
Created on November 13, 2020
Start designing with a free template
Discover more than 1500 professional designs like these:
View
Visual Presentation
View
Terrazzo Presentation
View
Colorful Presentation
View
Modular Structure Presentation
View
Chromatic Presentation
View
City Presentation
View
News Presentation
Explore all templates
Transcript
BC Box Addressing
Main BC Box addressing has to follow on from the Outdoor unit addressing sequence. If the main outdoor unit is addressed as 051 and there is only one outdoor unit, the main BC box would be address 052. If the system consisted of two outdoor units and one BC box the addressing would be:
Main BC Box
Outdoor Main - 051Outdoor Sub - 052 Main BC Box - 053
Sub BC Box Addressing
Sub BC Box
Sub BC Boxes are addressed according to the Lowest addressed Indoor Fan coil connected to the Sub Box(Lowest fan coil + 50) For Example: Main OC - 051 Sub OC - 052 Main BC - 053 Indoors connected to main BC 001 to 016 Indoors connected to Sub BC 017 to 020 Sub BC - 067 (017+50)
Lowest IC on Sub Box = 017017 + 50 = 067 Sub BC Box Address