Indoor Unit Addressing

Indoor addressing starts at adress number 1 and the highest indoor address you can assign is 50. The Addressing dials are labelled SW11 and SW12 The BC Box port address (when using R2 system) is SW14 For Example: If you wanted to set an indoor fan coil to address 15 and the refrigerant pipes were connected onto the BC box port 7, the dials would be set as follows SW11 - 5 (single digits address) SW12 - 1 (tens digit address) SW14 - 7 (port number)

Indoor Unit Addressing

Addressing Dials on Indoor PCB

Indoor 001 = Port 1Indoor 002 = Port 2 Indoor 003 = Port 4 Indoor 004 = Port 6

002

003

004

001

SW11=2SW12=0 SW14=2

SW11=3SW12=0 SW14=4

SW11=4SW12=0 SW14=6

SW11=1SW12=0 SW14=1