Outdoor Unit Addressing

The Outdoor unit addressing range is from 051 to 099 The Main Outdoor Unit has to be adressed 50+ the first indoor fan coil address The most common Outdoor unit address is 051 as stand alone systems usually start with Indoor fan coil address 001

Sub Outdoor units are addressed One digit higher than the Main Outdoor

OC = 051 when IC = 001

Outdoor Unit Addressing Dials

The Addressing Dials on the Outdoor Unit are labelled SWU1 and SWU2 SWU1 is the Single digits and SWU2 is the Tens To set address 051: SWU1 - set 1 SWU2 - set 5

Outdoor Unit Addressing

Multiple Outdoors on same System

001 002 003

051 052 053

Systems with Multiple Outdoor Units are addressed in sequence, with the Main OC 50+ the first IC address

Outdoor Unit Addressing

Multiple Outdoors on Seperate Systems

x5

x5

x5

011 to 015

006 to 010

001 to 005

056

061

051

Seperate systems installed on the same site should be addressed with individual addresses. Each OC 50+ the first IC address.