Outdoor Unit Piping

500mm of straight pipe required between each twinning kit or before the first bend

Outdoor Unit Piping

Outdoor Unit Piping

Outdoor Unit Piping

Maximum Height difference of 100mm between the Highest and Lowest Outdoor unit (H)

The Pipe work must flow downwards from the first outdoor unit into the building. Oil will get trapped at point A if the pipe work is inclined into the building

Downwards slope